Plug Fans (RLM Plenum Fans)

Plug fans (RLM / plenum fans) run without a scroll housing and mount directly inside the unit plenum — the most integrated format for AHU OEMs and fan-wall (FanGrid) arrays. EC versions accept 0–10 V / PWM speed control. Final selection is confirmed at the duty point (airflow / static pressure / voltage / control mode) and by project verification.

Filter by duty point6 models match · series LWBE3G400
Clear

Filters use nameplate maximum values (max airflow at zero static pressure, max static pressure at zero airflow). Check the actual operating point on the performance curve of each model.

ModelSizeMax airflowm³/hMax static pressurePaPowerWNoisedB(A)SpeedrpmVoltageV
LWBE3G400-102PS-01 LWBE3G400-102PS-01EC Ø400 mm 3,914 556 330 70 1,430 230 Details
LWBE3G400-102PS-09 LWBE3G400-102PS-09EC Ø400 mm 4,463 420 297 1,250 230 Details
LWBE3G400-102PS-10 LWBE3G400-102PS-10EC Ø400 mm 5,615 622 500 1,520 230 Details
LWBE3G400-102PS-11 LWBE3G400-102PS-11EC Ø400 mm 3,554 546 300 76 1,460 230 Details
LWBE3G400-138PT-04 LWBE3G400-138PT-04EC Ø400 mm 7,459 840 1,100 77 2,060 400 Details
LWBE3G400-188PT-07 LWBE3G400-188PT-07EC Ø400 mm 9,682 1,627 2,060 84 2,650 400 Details
Certifications for this product line
CE-LVD ×3ETL ×2CE-EMCRoHS ×3
View certificates →