Backward Curved Centrifugal Fans

Backward curved impellers give the best efficiency in the high static pressure region, suited to AHU, RTU, CRAH units and the clean side of dust collectors. The third-generation LWBE3G platform uses a bionic blade profile, covering impellers Ø190–710 mm and static pressures up to about 1,800 Pa. Final selection is confirmed at the duty point (airflow / static pressure / voltage / control mode) and by project verification.

Filter by duty point3 models match · series LWBA2E180
Clear

Filters use nameplate maximum values (max airflow at zero static pressure, max static pressure at zero airflow). Check the actual operating point on the performance curve of each model.

ModelSizeMax airflowm³/hMax static pressurePaPowerWNoisedB(A)SpeedrpmVoltageV
LWBA2E180-092NS-01 LWBA2E180-092NS-01AC Ø180 mm 443 335 52 63 2,550 230 Details
LWBA2E180-092NS-02 LWBA2E180-092NS-02AC Ø180 mm 494 371 66 66 2,850 230 Details
LWBA2E180-092NS-03 LWBA2E180-092NS-03AC Ø180 mm 443 335 52 63 2,560 230 Details
Certifications for this product line
CE-LVD ×3ETL ×2CE-EMCRoHS ×3
View certificates →
Ningbo Longwell Electric Technology Co., Ltd. · No. 100 Henan Road, Ditang, Yuyao, Ningbo, Chinasales@longwellfans.com · WhatsApp +86 183 5827 4663 · Mon–Fri 8:30–17:30 (UTC+8), reply within 1 business dayHow to order · Privacy notice