LWBA6D630-188NT-01 product photo
  • ImpellerØ630 mm24.8 in
  • Max airflow12,360 m³/h7,275 CFM
  • Max static pressure494 Pa1.98 in. wg
  • Voltage380 V
  • Speed900 rpm
  • Input power1,500 W2.01 hp
  • Noise80 dB(A)

LWBA6D630-188NT-01 AC Backward Curved Centrifugal Fan Ø630 mm

Ø630 mm | AC | Max airflow 12,360 m³/h | Max static pressure 494 Pa | 80 dB(A)

SKU: LWBA6D630-188NT-01 Categories: ,
  • Factory direct
  • OEM / ODM
  • Samples in 1–3 days
  • Production 15–30 days
  • 18-month warranty
  • CE · RoHS · ETL on request
View RFQ →

Digitised from the catalogue curve at standard air (20 °C, 101.3 kPa, 1.2 kg/m³); one curve per voltage / speed grade. The system resistance curve depends on the actual ductwork — confirm the operating point on site. Need an engineer to verify the duty point? Contact us or add the model to your RFQ and note the duty point.

Dimensional drawingDimensions in mm. Confirm against the final approval drawing before machining cut-outs.
LWBA6D630-188NT-01 Dimensional drawing

Downloads for LWBA6D630-188NT-01

PDFDatasheet · 1.9 MB

Need a non-standard size or another format? Ask an engineer or search the download center.

LWBA6D630-188NT-01 is a LONGWELL AC Backward Curved Centrifugal Fan from the Backward Curved Centrifugal Fans range, impeller Ø630 mm, rated 380 V AC, maximum airflow 12,360 m³/h, maximum static pressure 494 Pa, noise 80 dB(A), input power 1,500 W. The fixed-speed AC external-rotor motor is simple, robust and cost-effective for constant-duty applications.

Technical data

Model LWBA6D630-188NT-01
Series LWBA6D630
Motor type AC
Phase 3-phase
Rated voltage 380 V
Frequency 50 Hz
Current 3.8 A
Input power 1,500 W
Speed 900 rpm
Max. airflow 12,360 m³/h
Max. static pressure 494 Pa
Noise 80 dB(A)
Ambient temperature -40 ~ 65 °C
Impeller diameter Ø630 mm
Rotor diameter 188
Impeller material Aluminum Alloy
Protection class IP54
Insulation class F
Bearing Maintenance-free ball bearings
Duty S1
Rotation Clockwise,seen on rotor

Typical applications

  • Air handling units (AHU) and rooftop units (RTU)
  • Data-center CRAH / CRAC units and fan walls
  • Dust extraction and process ventilation
  • Fan filter units and air purifiers

Series LWBA6D630: models in the same series share the impeller and motor platform and differ in speed grade, voltage or lead-out / terminal-box configuration — compare them in the table below or ask for the best fit at your duty point.

Nameplate values: maximum airflow is measured at zero static pressure and maximum static pressure at zero airflow; the two never occur together. Confirm the operating point on the performance curve. Final selection is subject to the duty point (airflow / static pressure / voltage / control mode) and project verification.

Alternatives with the same impeller (Ø630 mm · AC)

Same impeller, different speed grade, power or wiring. Step up for more airflow, step down for lower noise.

ModelMax airflowMax static pressureSpeedPowerNoiseVoltage
LWBA6D630-188NT-01 this model 12,360 m³/h494 Pa 900 rpm1,500 W80 dB(A)380 V
LWBA8D630-188NT-02 9,270 m³/h288 Pa 700 rpm700 W72 dB(A)380 V View
LWBA4D630-188NT-03 17,955 m³/h956 Pa 1,210 rpm3,320 W86.9 dB(A)380 V View

Not sure which one? Send us the duty point (airflow / static pressure / noise limit) — use the selector or ask an engineer.

Ningbo Longwell Electric Technology Co., Ltd. · No. 100 Henan Road, Ditang, Yuyao, Ningbo, Chinasales@longwellfans.com · WhatsApp +86 183 5827 4663 · Mon–Fri 8:30–17:30 (UTC+8), reply within 1 business dayHow to order · Privacy notice