LWFA-E-250-01 product photo
LWFA-E-250-01 product photo
  • ImpellerØ250 mm9.8 in
  • Max airflow2,500 m³/h1,471 CFM
  • Max static pressure380 Pa1.53 in. wg
  • Noise70 dB(A)

LWFA-E-250-01 LWFA Series Direct Drive Centrifugal Blower Ø250 mm

Ø250 mm | AC | Max airflow 2,500 m³/h | Max static pressure 380 Pa | 70 dB(A)

  • Factory direct
  • OEM / ODM
  • Samples in 1–3 days
  • Production 15–30 days
  • 18-month warranty
  • CE · RoHS · ETL on request
View RFQ →

Digitised from the catalogue curve at standard air (20 °C, 101.3 kPa, 1.2 kg/m³); one curve per voltage / speed grade. The system resistance curve depends on the actual ductwork — confirm the operating point on site. Need an engineer to verify the duty point? Contact us or add the model to your RFQ and note the duty point.

Dimensional drawingDimensions in mm. Confirm against the final approval drawing before machining cut-outs.
LWFA-E-250-01 Dimensional drawing
Performance curve (P-Q)Static pressure vs. airflow. Curve numbers correspond to supply voltage / speed grades.
LWFA-E-250-01 Performance curve (P-Q)
Wiring diagramLead colours and terminal assignment; TK = motor thermal contact.
LWFA-E-250-01 Wiring diagram

Downloads for LWFA-E-250-01

PDFDatasheet · 959 KB

Series catalogue

PDFLWFA LWFA Series Direct Driven centrifugal blower · 1.4 MB

Covers the whole series, not only this model.

Need a non-standard size or another format? Ask an engineer or search the download center.

LWFA-E-250-01 is a LONGWELL LWFA Series Direct Drive Centrifugal Blower from the Impeller Ø178–254 mm range, impeller Ø250 mm, maximum airflow 2,500 m³/h, maximum static pressure 380 Pa, noise 70 dB(A). The fixed-speed AC external-rotor motor is simple, robust and cost-effective for constant-duty applications.

Technical data

Model LWFA-E-250-01
Motor type AC
Max. airflow 2,500 m³/h
Max. static pressure 380 Pa
Noise 70 dB(A)
Storage temperature -40 ~ 80℃
Humidity 0 ~ 90 % RH
Altitude < 1000m
Impeller diameter Ø250 mm
Blade diameter 250mm
Impeller material Galvanized sheet ( Impeller )
Balance grade G6.3
Vibration standard JB/T 8689
Service life 30,000Hours(L10), At 40 °Croom, humidity 15%~65%RH

Typical applications

  • Commercial kitchen extraction
  • Ventilation units and AHUs
  • Process and fume extraction

Nameplate values: maximum airflow is measured at zero static pressure and maximum static pressure at zero airflow; the two never occur together. Confirm the operating point on the performance curve. Final selection is subject to the duty point (airflow / static pressure / voltage / control mode) and project verification.

Alternatives with the same impeller (Ø250 mm · AC)

Same impeller, different speed grade, power or wiring. Step up for more airflow, step down for lower noise.

ModelMax airflowMax static pressureSpeedPowerNoiseVoltage
LWFA-E-250-01 this model 2,500 m³/h380 Pa 70 dB(A)
LWFA-E-250-02 2,100 m³/h215 Pa 64 dB(A) View

Not sure which one? Send us the duty point (airflow / static pressure / noise limit) — use the selector or ask an engineer.

Ningbo Longwell Electric Technology Co., Ltd. · No. 100 Henan Road, Ditang, Yuyao, Ningbo, Chinasales@longwellfans.com · WhatsApp +86 183 5827 4663 · Mon–Fri 8:30–17:30 (UTC+8), reply within 1 business dayHow to order · Privacy notice
Scroll to Top
RFQ list