LWFA-E-450-02 product photo
LWFA-E-450-02 product photo
  • ImpellerØ450 mm17.7 in
  • Max airflow10,500 m³/h6,180 CFM
  • Max static pressure750 Pa3.01 in. wg
  • Noise80 dB(A)

LWFA-E-450-02 LWFA Series Direct Drive Centrifugal Blower Ø450 mm

Ø450 mm | AC | Max airflow 10,500 m³/h | Max static pressure 750 Pa | 80 dB(A)

  • Factory direct
  • OEM / ODM
  • Samples in 1–3 days
  • Production 15–30 days
  • 18-month warranty
  • CE · ETL · RoHS
View RFQ →

Digitised from the catalogue curve at standard air (20 °C, 101.3 kPa, 1.2 kg/m³); one curve per voltage / speed grade. The system resistance curve depends on the actual ductwork — confirm the operating point on site. Need an engineer to verify the duty point? Contact us or add the model to your RFQ and note the duty point.

Dimensional drawingDimensions in mm. Confirm against the final approval drawing before machining cut-outs.
LWFA-E-450-02 Dimensional drawing
Performance curve (P-Q)Static pressure vs. airflow. Curve numbers correspond to supply voltage / speed grades.
LWFA-E-450-02 Performance curve (P-Q)

Series catalogue

PDFLWFA LWFA Series Direct Driven centrifugal blower · 1.4 MB

Covers the whole series, not only this model.

Need a non-standard size or another format? Ask an engineer or search the download center.

LWFA-E-450-02 is a LONGWELL LWFA Series Direct Drive Centrifugal Blower from the Impeller Ø280–500 mm range, impeller Ø450 mm, maximum airflow 10,500 m³/h, maximum static pressure 750 Pa, noise 80 dB(A). The fixed-speed AC external-rotor motor is simple, robust and cost-effective for constant-duty applications.

Technical data

Model LWFA-E-450-02
Motor type AC
Max. airflow 10,500 m³/h
Max. static pressure 750 Pa
Noise 80 dB(A)
Impeller diameter Ø450 mm
Blade diameter 450mm

Typical applications

  • Commercial kitchen extraction
  • Ventilation units and AHUs
  • Process and fume extraction

Nameplate values: maximum airflow is measured at zero static pressure and maximum static pressure at zero airflow; the two never occur together. Confirm the operating point on the performance curve. Final selection is subject to the duty point (airflow / static pressure / voltage / control mode) and project verification.

Alternatives with the same impeller (Ø450 mm · AC)

Same impeller, different speed grade, power or wiring. Step up for more airflow, step down for lower noise.

ModelMax airflowMax static pressureSpeedPowerNoiseVoltage
LWFA-E-450-02 this model 10,500 m³/h750 Pa 80 dB(A)
LWBA6D450-138NT-07 4,017 m³/h309 Pa 920 rpm300 W60 dB(A)380 V View
LWBA6E450-138NS-05 4,017 m³/h309 Pa 930 rpm260 W60 dB(A)230 V View
LWBA4D450-138NT-08 4,450 m³/h381 Pa 1,050 rpm360 W61 dB(A)380 V View
LWBA6E450-138NS-06 4,450 m³/h381 Pa 1,050 rpm350 W61 dB(A)230 V View
LWBA4E450-138NS-02 6,077 m³/h618 Pa 1,350 rpm800 W76 dB(A)230 V View
LWBA4D450-138NT-01 6,077 m³/h618 Pa 1,350 rpm800 W76 dB(A)380 V View
LWBA4D450-138NT-09 6,164 m³/h630 Pa 1,395 rpm616 W78.8 dB(A)380 V View
LWFA-E-450-01 6,230 m³/h710 Pa 72 dB(A) View
LWEA450S(T)M-163E 6,658 m³/h150 Pa 1,450 rpm550 W220 V View
LWBA4D450-188NT-03 6,695 m³/h618 Pa 1,350 rpm800 W79 dB(A)380 V View
LWBA4D450-188NT-04 7,210 m³/h695 Pa 1,400 rpm1,100 W82 dB(A)380 V View
LWFA8D450-188NT-02 7,416 m³/h370.8 Pa 680 rpm2,000 W68 dB(A)380 V View
LWFA6D450-188NT-01 7,725 m³/h638.6 Pa 930 rpm3,500 W74 dB(A)380 V View
LWA-450(18")U(S)M-01 12,500 m³/h580 Pa 2,800 rpm1,500 W110-120 V View

Not sure which one? Send us the duty point (airflow / static pressure / noise limit) — use the selector or ask an engineer.

Scroll to Top
RFQ list