LWFA-E-450-02 product photo
LWFA-E-450-02 product photo
  • ImpellerØ450 mm17.7 in
  • Max airflow10,500 m³/h6,180 CFM
  • Max static pressure750 Pa3.01 in. wg
  • Noise80 dB(A)

LWFA-E-450-02 LWFA Series Direct Drive Centrifugal Blower Ø450 mm

Ø450 mm | AC | Max airflow 10,500 m³/h | Max static pressure 750 Pa | 80 dB(A)

  • Factory direct
  • OEM / ODM
  • Samples in 1–3 days
  • Production 15–30 days
  • 18-month warranty
  • CE · RoHS · ETL on request
View RFQ →

Digitised from the catalogue curve at standard air (20 °C, 101.3 kPa, 1.2 kg/m³); one curve per voltage / speed grade. The system resistance curve depends on the actual ductwork — confirm the operating point on site. Need an engineer to verify the duty point? Contact us or add the model to your RFQ and note the duty point.

Dimensional drawingDimensions in mm. Confirm against the final approval drawing before machining cut-outs.
LWFA-E-450-02 Dimensional drawing
Performance curve (P-Q)Static pressure vs. airflow. Curve numbers correspond to supply voltage / speed grades.
LWFA-E-450-02 Performance curve (P-Q)

Series catalogue

PDFLWFA LWFA Series Direct Driven centrifugal blower · 1.4 MB

Covers the whole series, not only this model.

Need a non-standard size or another format? Ask an engineer or search the download center.

LWFA-E-450-02 is a LONGWELL LWFA Series Direct Drive Centrifugal Blower from the Impeller Ø280–500 mm range, impeller Ø450 mm, maximum airflow 10,500 m³/h, maximum static pressure 750 Pa, noise 80 dB(A). The fixed-speed AC external-rotor motor is simple, robust and cost-effective for constant-duty applications.

Technical data

Model LWFA-E-450-02
Motor type AC
Max. airflow 10,500 m³/h
Max. static pressure 750 Pa
Noise 80 dB(A)
Impeller diameter Ø450 mm
Blade diameter 450mm

Typical applications

  • Commercial kitchen extraction
  • Ventilation units and AHUs
  • Process and fume extraction

Nameplate values: maximum airflow is measured at zero static pressure and maximum static pressure at zero airflow; the two never occur together. Confirm the operating point on the performance curve. Final selection is subject to the duty point (airflow / static pressure / voltage / control mode) and project verification.

Alternatives with the same impeller (Ø450 mm · AC)

Same impeller, different speed grade, power or wiring. Step up for more airflow, step down for lower noise.

ModelMax airflowMax static pressureSpeedPowerNoiseVoltage
LWFA-E-450-02 this model 10,500 m³/h750 Pa 80 dB(A)
LWFA-E-450-01 6,230 m³/h710 Pa 72 dB(A) View

Not sure which one? Send us the duty point (airflow / static pressure / noise limit) — use the selector or ask an engineer.

Ningbo Longwell Electric Technology Co., Ltd. · No. 100 Henan Road, Ditang, Yuyao, Ningbo, Chinasales@longwellfans.com · WhatsApp +86 183 5827 4663 · Mon–Fri 8:30–17:30 (UTC+8), reply within 1 business dayHow to order · Privacy notice
Scroll to Top
RFQ list