Centrifugal Fans

Filter by duty point614 models in this category

Filters use nameplate maximum values (max airflow at zero static pressure, max static pressure at zero airflow). Check the actual operating point on the performance curve of each model.

ModelSizeMax airflowm³/hMax static pressurePaPowerWNoisedB(A)SpeedrpmVoltageV
LWFD3G197-072DZ-01 LWFD3G197-072DZ-01DC Ø197 mm 1,197 525 85 750 310 Details
LWFE3G108-072NS-01 LWFE3G108-072NS-01EC Ø108 mm 330 330 82 57 3,340 230 Details
LWFE3G120-072DS-01 LWFE3G120-072DS-01EC Ø120 mm 433 263 70 59 1,900 230 Details
LWFE3G120-072NS-01 LWFE3G120-072NS-01EC Ø120 mm 350 412 90 67 3,230 230 Details
LWFE3G120-072SS-01 LWFE3G120-072SS-01EC Ø120 mm 268 443 42 60 2,200 230 Details
LWFE3G120-072SS-02 LWFE3G120-072SS-02EC Ø120 mm 361 649 75 61 3,650 230 Details
LWFE3G133-072DS-01 LWFE3G133-072DS-01EC Ø133 mm 773 288 105 69 1,750 230 Details
LWFE3G133-072DS-02 LWFE3G133-072DS-02EC Ø133 mm 979 484 120 70 1,450 230 Details
LWFE3G133-072NS-01 LWFE3G133-072NS-01EC Ø133 mm 433 288 85 63 2,290 230 Details
LWFE3G133-072PS-02 LWFE3G133-072PS-02EC Ø133 mm 267.8 453.2 30 63 3,800 230 Details
LWFE3G133-072PS-03 LWFE3G133-072PS-03EC Ø133 mm 432.6 432.6 53 70 4,400 230 Details
LWFE3G133-072SS-01 LWFE3G133-072SS-01EC Ø133 mm 319 191 65 68 2,050 230 Details
LWFE3G133-092DS-03 LWFE3G133-092DS-03EC Ø133 mm 690 330 80 69 1,550 230 Details
LWFE3G140-072NS-01 LWFE3G140-072NS-01EC Ø140 mm 484 216 70 72 1,910 230 Details
LWFE3G140-072NS-02 LWFE3G140-072NS-02EC Ø140 mm 494 845 115 74 2,060 230 Details
LWFE3G140-072SS-01 LWFE3G140-072SS-01EC Ø140 mm 453 783 85 72 1,860 230 Details
LWFE3G140-072SS-02 LWFE3G140-072SS-02EC Ø140 mm 505 881 85 61 1,900 230 Details
LWFE3G140-072SS-03 LWFE3G140-072SS-03EC Ø140 mm 597 979 110 65 2,030 230 Details
LWFE3G140-072SS-04 LWFE3G140-072SS-04EC Ø140 mm 597 979 110 65 2,130 230 Details
LWFE3G146-072DS-01 LWFE3G146-072DS-01EC Ø146 mm 989 474 120 72 1,350 230 Details
LWFE3G146-072DS-04 LWFE3G146-072DS-04EC Ø146 mm 752 567 115 66 2,400 230 Details
LWFE3G146-092DS-02 LWFE3G146-092DS-02EC Ø146 mm 855 536 80 59 1,300 230 Details
LWFE3G146-092DS-03 LWFE3G146-092DS-03EC Ø146 mm 1,009 670 115 61 1,450 230 Details
LWFE3G146-092DS-05 LWFE3G146-092DS-05EC Ø146 mm 1,133 876 220 74 3,200 230 Details
LWFE3G150-092SS-01 LWFE3G150-092SS-01EC Ø150 mm 577 412 150 72 2,550 230 Details
LWFE3G160-072NS-01 LWFE3G160-072NS-01EC Ø160 mm 639 906 115 64 1,800 230 Details
LWFE3G160-072NS-02 LWFE3G160-072NS-02EC Ø160 mm 649 989 155 68 3,050 230 Details
LWFE3G160-072SS-03 LWFE3G160-072SS-03EC Ø160 mm 597 876 115 67 2,760 230 Details
LWFE3G160-072SS-04 LWFE3G160-072SS-04EC Ø160 mm 649 989 155 68 3,050 230 Details
LWFE3G160-072SS-06 LWFE3G160-072SS-06EC Ø160 mm 639 906 115 64 1,800 230 Details
LWFE3G160-072SS-07 LWFE3G160-072SS-07EC Ø160 mm 670 979 170 67 3,050 230 Details
LWFE3G160-092NS-03 LWFE3G160-092NS-03EC Ø160 mm 803 927 230 75 3,300 230 Details
LWFE3G160-092SS-01 LWFE3G160-092SS-01EC Ø160 mm 680 556 240 72 2,500 230 Details
LWFE3G160-092SS-02 LWFE3G160-092SS-02EC Ø160 mm 666 773 143 1,905 230 Details
LWFE3G160-092SS-05 LWFE3G160-092SS-05EC Ø160 mm 803 927 230 75 3,300 230 Details
LWFE3G160-092SS-08 LWFE3G160-092SS-08EC Ø160 mm 814 824 230 73 3,370 230 Details
LWFE3G175-072PS-01 LWFE3G175-072PS-01EC Ø175 mm 535.6 453.2 55 65 2,800 230 Details
LWFE3G175-072PS-02 LWFE3G175-072PS-02EC Ø175 mm 741.6 535.6 85 72 3,300 230 Details
LWFE3G175-072PS-03 LWFE3G175-072PS-03EC Ø175 mm 700.4 803.4 115 74 4,400 230 Details
LWFE3G175-072PS-04 LWFE3G175-072PS-04EC Ø175 mm 911.55 875.5 170 71 4,760 230 Details
Certifications for this product line
CE-LVD ×3ETL ×2CE-EMCRoHS ×3
View certificates →

Centrifugal Fans — selection guide

Centrifugal Fans: 614 models, impellers Ø108–630 mm, maximum airflow 155–23,896 m³/h, static pressure to 5,401 Pa, EC, AC and DC motors, across 137 series. 525 of them carry a measured P-Q curve and 572 a dimensional drawing.

LONGWELL's centrifugal range is organised by impeller type rather than by application, because the impeller decides the shape of the curve. Backward curved impellers (LWBE3G EC, LWBA AC, LWBD3G DC) hold the high-pressure end and are non-overloading; forward curved multi-vane impellers (LWFE3G EC, LWFA AC, LWFD3G DC) give more airflow per diameter at low pressure; and plug fans are backward curved impellers supplied without a scroll for plenum mounting. The whole family shares the same motor platforms — rotor sizes 92, 102 and 138 on external-rotor motors — so a duty point can usually be met by more than one impeller type, and the selector shows them side by side.

Impeller material follows size: PA66 or PA66-GF up to about Ø225 mm, aluminium alloy from Ø250 mm and galvanised steel for the scroll housings. Supply voltages run from 24 / 48 V DC through 115 / 230 V single-phase to 380 / 400 V three-phase, which is why the same duty can be quoted for a battery-powered unit, a European AHU and a North American rooftop unit.

How to select from this range

  1. Fix the duty point first: airflow plus the static pressure of the whole system at that airflow, including dirty-filter allowance. Nameplate maximum airflow and maximum pressure are two different points on the curve and are never reached together.
  2. Above roughly 300 Pa go backward curved; below that a forward curved blower of the same diameter usually moves more air in a smaller housing.
  3. For AHU plenums and fan walls use plug fans — no scroll, no discharge duct, and EC control as standard.
  4. Pick the motor platform by duty profile: EC for modulating loads and BMS integration (about 30% lower consumption at part load, confirmed against the load profile), AC for constant duty at lowest first cost, DC for 24 / 48 V equipment.
  5. Check the curve margin the selector reports: 10–25% is the target, below 8% is flagged.

Where these fans are used

  • Air handling units and rooftop units
  • Data-center CRAH units and fan walls
  • Dust extraction and fume systems
  • Fan coil units and compact air conditioners
  • Ovens, dryers and process equipment

Every figure above is measured on our own test rigs per AMCA 210 / ISO 5801 methods — see the test labs and certificates. Final selection is confirmed at the duty point and by project validation.

FAQ — Centrifugal Fans

How do backward curved, forward curved and plug fans differ in the LONGWELL range?

Backward curved (LWBE3G / LWBA) impellers give the highest static efficiency and a power curve that falls off at high airflow, so the motor cannot overload. Forward curved (LWFE3G / LWFA / LWFD3G) impellers move more air from a given diameter at low pressure but need a scroll housing. Plug fans are backward curved impellers on an inlet cone without a scroll, for mounting inside a plenum.

Which rotor size should I specify — 92, 102 or 138?

The rotor number is the external-rotor motor size. It fixes the available shaft power and therefore the top of the curve for a given impeller: the same Ø355 impeller is offered on 102 and 138 rotors with different maximum pressure. The selector picks the smallest motor that clears your duty point with margin.

Can one duty point be met by more than one centrifugal type?

Often yes. A 3,000 m³/h at 400 Pa duty can be met by a Ø310 backward curved fan, a Ø280 plug fan or a Ø250 dual-inlet forward blower, with different noise, envelope and efficiency. The selector lists all of them; the choice is then about installation format and control.

Are the centrifugal fans available in 115 V for North America?

Yes. The backward curved and forward curved lines include 115 V single-phase versions, and the DC and EC centrifugal lines carry ETL listing (Intertek control no. 5022563) for UL 507 / CSA C22.2 No. 113.

Related selections

Scroll to Top
RFQ list