Centrifugal Fans

Filter by duty point614 models in this category

Filters use nameplate maximum values (max airflow at zero static pressure, max static pressure at zero airflow). Check the actual operating point on the performance curve of each model.

ModelSizeMax airflowm³/hMax static pressurePaPowerWNoisedB(A)SpeedrpmVoltageV
LWFA2E133-092DS-08 LWFA2E133-092DS-08AC Ø133 mm 726.15 381.1 190 60 1,500 230 Details
LWFA2E133-092DS-10 LWFA2E133-092DS-10AC Ø133 mm 773 433 250 58 1,200 230 Details
LWFA2E133-092NS-01 LWFA2E133-092NS-01AC Ø133 mm 299 361 83 61 2,300 230 Details
LWFA2E133-092NS-02 LWFA2E133-092NS-02AC Ø133 mm 278 464 95 63 2,350 230 Details
LWFA2E133-092SS-01 LWFA2E133-092SS-01AC Ø133 mm 299 361 83 61 1,850 230 Details
LWFA2E133-092SS-02 LWFA2E133-092SS-02AC Ø133 mm 278 464 95 63 1,750 230 Details
LWFA2E133-092SS-03 LWFA2E133-092SS-03AC Ø133 mm 319 433 85 56 1,600 230 Details
LWFA2E140-092NS-01 LWFA2E140-092NS-01AC Ø140 mm 335 330 100 52 1,600 230 Details
LWFA2E140-092NS-02 LWFA2E140-092NS-02AC Ø140 mm 314 484 110 58 1,500 230 Details
LWFA2E140-092NS-03 LWFA2E140-092NS-03AC Ø140 mm 340 371 100 52 1,600 230 Details
LWFA2E140-092SS-01 LWFA2E140-092SS-01AC Ø140 mm 446.25 378 148 65 2,400 230 Details
LWFA2E140-092SS-02 LWFA2E140-092SS-02AC Ø140 mm 335 433 90 52 1,400 230 Details
LWFA2E146-092DS-01 LWFA2E146-092DS-01AC Ø146 mm 742 453 175 58 950 230 Details
LWFA2E146-092DS-02 LWFA2E146-092DS-02AC Ø146 mm 700 515 190 58 900 230 Details
LWFA2E146-092DS-03 LWFA2E146-092DS-03AC Ø146 mm 1,009 494 275 69 1,300 230 Details
LWFA2E146-092DS-04 LWFA2E146-092DS-04AC Ø146 mm 948 597 295 69 1,200 230 Details
LWFA2E146-092DS-05 LWFA2E146-092DS-05AC Ø146 mm 927 515 250 60 1,500 230 Details
LWFA2E146-092DS-07 LWFA2E146-092DS-07AC Ø146 mm 479 391 105 40 1,380 230 Details
LWFA2E146-092DS-08 LWFA2E146-092DS-08AC Ø146 mm 639 536 250 56 1,120 230 Details
LWFA2E146-092DS-09 LWFA2E146-092DS-09AC Ø146 mm 762 5,401 260 60 1,370 230 Details
LWFA2E146-092DS-10 LWFA2E146-092DS-10AC Ø146 mm 736 515 235 57 1,380 230 Details
LWFA2E146-092DS-11 LWFA2E146-092DS-11AC Ø146 mm 587 314 125 61 1,500 230 Details
LWFA2E146-092DS-12 LWFA2E146-092DS-12AC Ø146 mm 876 597 288 72 1,770 230 Details
LWFA2E146-092DS-13 LWFA2E146-092DS-13AC Ø146 mm 886 464 298 73 1,984 230 Details
LWFA2E150-092NS-01 LWFA2E150-092NS-01AC Ø150 mm 551 464 135 67 2,600 230 Details
LWFA2E150-092NS-02 LWFA2E150-092NS-02AC Ø150 mm 500 649 180 71 2,850 230 Details
LWFA2E150-092SS-01 LWFA2E150-092SS-01AC Ø150 mm 546 464 183 63 2,300 230 Details
LWFA2E150-092SS-02 LWFA2E150-092SS-02AC Ø150 mm 494 639 230 68 2,200 230 Details
LWFA2E160-092NS-01 LWFA2E160-092NS-01AC Ø160 mm 525 556.2 230 69 1,800 230 Details
LWFA2E160-092SS-01 LWFA2E160-092SS-01AC Ø160 mm 619.5 577.5 222 65 2,020 230 Details
LWFA2E160-092SS-03 LWFA2E160-092SS-03AC Ø160 mm 453 608 150 57 1,450 230 Details
LWFA2E160-092SS-04 LWFA2E160-092SS-04AC Ø160 mm 525 618 220 61 1,800 230 Details
LWFA2E180-092SS-03 LWFA2E180-092SS-03AC Ø180 mm 742 670 300 73 2,000 230 Details
LWFA4D200-102NT-01 LWFA4D200-102NT-01AC Ø200 mm 1,236 226.6 330 59 1,270 380 Details
LWFA4D225-138NT-01 LWFA4D225-138NT-01AC Ø225 mm 1,648 288.4 490 65 1,300 380 Details
LWFA4D225-138ST-02 LWFA4D225-138ST-02AC Ø225 mm 1,442 288.4 400 73 1,390 380 Details
LWFA4D250-102DS-04 LWFA4D250-102DS-04AC Ø250 mm 4,161.2 412 1,200 77 1,250 380 Details
LWFA4D250-102DS-05 LWFA4D250-102DS-05AC Ø250 mm 5,226.75 383.8 1,380 77 1,360 380 Details
LWFA4D250-138NT-01 LWFA4D250-138NT-01AC Ø250 mm 2,369 406.85 870 72 1,400 380 Details
LWFA4D250-138ST-01 LWFA4D250-138ST-01AC Ø250 mm 3,399 391.4 850 80 1,350 380 Details
Certifications for this product line
CE-LVD ×3ETL ×2CE-EMCRoHS ×3
View certificates →

Centrifugal Fans — selection guide

Centrifugal Fans: 614 models, impellers Ø108–630 mm, maximum airflow 155–23,896 m³/h, static pressure to 5,401 Pa, EC, AC and DC motors, across 137 series. 525 of them carry a measured P-Q curve and 572 a dimensional drawing.

LONGWELL's centrifugal range is organised by impeller type rather than by application, because the impeller decides the shape of the curve. Backward curved impellers (LWBE3G EC, LWBA AC, LWBD3G DC) hold the high-pressure end and are non-overloading; forward curved multi-vane impellers (LWFE3G EC, LWFA AC, LWFD3G DC) give more airflow per diameter at low pressure; and plug fans are backward curved impellers supplied without a scroll for plenum mounting. The whole family shares the same motor platforms — rotor sizes 92, 102 and 138 on external-rotor motors — so a duty point can usually be met by more than one impeller type, and the selector shows them side by side.

Impeller material follows size: PA66 or PA66-GF up to about Ø225 mm, aluminium alloy from Ø250 mm and galvanised steel for the scroll housings. Supply voltages run from 24 / 48 V DC through 115 / 230 V single-phase to 380 / 400 V three-phase, which is why the same duty can be quoted for a battery-powered unit, a European AHU and a North American rooftop unit.

How to select from this range

  1. Fix the duty point first: airflow plus the static pressure of the whole system at that airflow, including dirty-filter allowance. Nameplate maximum airflow and maximum pressure are two different points on the curve and are never reached together.
  2. Above roughly 300 Pa go backward curved; below that a forward curved blower of the same diameter usually moves more air in a smaller housing.
  3. For AHU plenums and fan walls use plug fans — no scroll, no discharge duct, and EC control as standard.
  4. Pick the motor platform by duty profile: EC for modulating loads and BMS integration (about 30% lower consumption at part load, confirmed against the load profile), AC for constant duty at lowest first cost, DC for 24 / 48 V equipment.
  5. Check the curve margin the selector reports: 10–25% is the target, below 8% is flagged.

Where these fans are used

  • Air handling units and rooftop units
  • Data-center CRAH units and fan walls
  • Dust extraction and fume systems
  • Fan coil units and compact air conditioners
  • Ovens, dryers and process equipment

Every figure above is measured on our own test rigs per AMCA 210 / ISO 5801 methods — see the test labs and certificates. Final selection is confirmed at the duty point and by project validation.

FAQ — Centrifugal Fans

How do backward curved, forward curved and plug fans differ in the LONGWELL range?

Backward curved (LWBE3G / LWBA) impellers give the highest static efficiency and a power curve that falls off at high airflow, so the motor cannot overload. Forward curved (LWFE3G / LWFA / LWFD3G) impellers move more air from a given diameter at low pressure but need a scroll housing. Plug fans are backward curved impellers on an inlet cone without a scroll, for mounting inside a plenum.

Which rotor size should I specify — 92, 102 or 138?

The rotor number is the external-rotor motor size. It fixes the available shaft power and therefore the top of the curve for a given impeller: the same Ø355 impeller is offered on 102 and 138 rotors with different maximum pressure. The selector picks the smallest motor that clears your duty point with margin.

Can one duty point be met by more than one centrifugal type?

Often yes. A 3,000 m³/h at 400 Pa duty can be met by a Ø310 backward curved fan, a Ø280 plug fan or a Ø250 dual-inlet forward blower, with different noise, envelope and efficiency. The selector lists all of them; the choice is then about installation format and control.

Are the centrifugal fans available in 115 V for North America?

Yes. The backward curved and forward curved lines include 115 V single-phase versions, and the DC and EC centrifugal lines carry ETL listing (Intertek control no. 5022563) for UL 507 / CSA C22.2 No. 113.